Table Of Contents

DAQmx Create Virtual Channel (Counter Output » Pulse Ticks) (G Dataflow)

Version:
    Last Modified: February 6, 2017

    Creates channel(s) to generate digital pulses defined by the number of timebase ticks that the pulse is at a high state and the number of timebase ticks that the pulse is at a low state. The pulses appear on the default output terminal of the counter, unless you select a different output terminal.

    connector_pane_image
    datatype_icon

    task in

    task in specifies the task to which to add the virtual channels this node creates. If you do not specify a task, NI-DAQmx creates a task for you, and adds the virtual channels this node creates to that task.

    datatype_icon

    counter

    counter specifies the names of the counters to use to create the virtual channels. The DAQmx physical channel constant lists all physical channels, including counters, for devices installed in the system.

    You also can wire a string that contains a list, or range of counters, to this input. If you have an array of counters, use the DAQmx Flatten Channel String node to convert the array to a list.

    datatype_icon

    name to assign

    name to assign specifies a name to assign to the virtual channel this node creates. If you do not wire a value to this input, NI-DAQmx uses the physical channel name as the virtual channel name.

    If you use this input to provide your own names for the virtual channels, you must use the names when you refer to these channels in other NI-DAQmx nodes, such as the source input of the DAQmx Trigger node.

    If you create multiple virtual channels with one DAQmx Create Virtual Channel node, you can specify a comma-separated list of names to assign to the virtual channels. If you provide fewer names than the number of virtual channels you create, NI-DAQmx automatically assigns names to the virtual channels.

    datatype_icon

    source of ticks

    source of ticks is the terminal to which you connect an external timebase. A DAQmx terminal constant lists all terminals available on devices installed in the system. You also can specify a source terminal by wiring a string that contains a terminal name.

    datatype_icon

    error in

    error in describes error conditions that occur before this node runs. This input provides standard 'error in' functionality.

    datatype_icon

    high ticks

    high ticks is the number of ticks the pulse is high.

    datatype_icon

    low ticks

    low ticks is the number of ticks the pulse is low.

    datatype_icon

    idle state

    idle state specifies the resting state of the output terminal.

    Name Description
    High

    Terminal is at a high state at rest.

    Low

    Terminal is at a low state at rest.

    datatype_icon

    initial delay

    initial delay is the number of timebase ticks to wait before generating the first pulse.

    datatype_icon

    task out

    task out is a reference to the task after this node runs. The task contains any newly created virtual channels. If you did not wire a value to task in, NI-DAQmx automatically creates the task this output refers to.

    datatype_icon

    error out

    error out contains error information. If error in indicates that an error occurred before this node ran, error out contains the same error information. Otherwise, error out describes the error status that this node produces.

    Where This Node Can Run:

    Desktop OS: Windows

    FPGA: LabVIEW NXG does not support FPGA devices


    Recently Viewed Topics